The HVW20D is a 20A DC resistance test of a transformer and is a necessary measuring item in the testing, installation, commissioning testing and electric power department’s preventive testing of semi-finished products and finished products in transformer manufacturing.
It can be used to effectively detect the selection of transformer coils, welding, loose connection parts, missing strands, broken wires, etc.
The instrument is small in size, light weight, large output current, etc. It is optimized for measuring the three-phase winding DC resistances of large-capacity transformers.
The instrument can be used to measure the three-phase winding DC resistances of a transformer at the same time.
For an on-load tap changing transformer, there is no need for discharging and tapping is directly adjusted with the instrument; the measuring time is 1/3 of traditional single-phase measuring time, which can greatly shorten testing time.
The tester has a Three Phase Test function to measure the three-phase DC resistance of the starconnected windings synchronously and calculate the three-phase unbalance rate automatically, so as to greatly reduce the measurement period and improve the test efficiency. Its phase-by-phase test function can also be used for phase-by-phase test on transformers with YN and D (Y) connections;
The winding material can be set according to the winding material of the transformer, such as copper or aluminum, to distinguish the conversion temperature coefficient of different materials.
The tester is equipped with transformer YN winding neutral point lead line resistance detection function, can make three-phase test data closer to the singlephase test value.
The tester is equipped with a USB port, to transfer test data onto a flash disk
The tester has storage to save 100 groups of data, review, and printing functions of test data
The tester has more complete parameter settings, including test windings, Tapping Positions, test phases, Tested Sample Temperature, Conversion Temperature and others of the transformers