The
range includes primary and
secondary current injection
equipment up 6000A, voltage
sources, micro-ohmmeters and
high voltage test systems up to
100kV.
|
|
|
|
The
PT18-10 and PT30-10 high voltage
dc test sets are designed to
perform tests on installed cable
and jointing systems. The units
have a variable output voltage
with a maximum or ±18kVdc
(PT18-10) or ±30kVdc (PT30-10).
Both units have a maximum
charging capability of 10mA. A
zero-volt interlock is fitted
that prevents the output being
switched on unless the output
control is at zero.
|
|
|
|
The
units include an automatic load
discharge system that discharges
the cable under test when the
output is switched off or a
breakdown occurs. The internal
dumping system can discharge a
maximum of 2.5kJ on each output,
corresponding to 10F at
18kV or 4F at 30kV. In
the event of a test object
failure, the overload circuit
will automatically switch off
the output voltage and earth the
output via the internal
discharge circuit. A manual
discharge probe is also supplied
as standard with both units,
allowing higher load
capacitances to be safely
discharged.
|
|
|
|
The
mk2 units introduce automatic
115/230V mains voltage
selection, allowing easy
transition between site
voltages.
|
|
|
|
The
output voltage is metered by two
large, linear, analogue
instruments marked 0-20kV
(PT18-10) or 0-30kV (PT30-10).
Test object current is metered
by two further analogue
instruments with 0-10 scale
marking. The meters read 0-10mA
directly, or 0-1mA when the ¸10
push button is operated.
|
|
|
|
The
HV output from the unit uses a
high quality plug and socket
system, allowing for easy cable
replacement.
|