The
D3R/D6R/D12R
Digital winding
tester can perform
Resistance, HiPot
and Surge tests as
well as digitize
and store data for
future use. |
|
|
 |
The
resistance test
verifies the
existence of dead
shorts within the
turn-to-turn
coils, shows any
imbalances between
phased due to
turns count
differences, along
with locating poor
wire connections
or contacts.
|
|
|
 |
DC
HiPot testing
detects faults in
groundwall/earth
insulation, and
also provides a
complete
Polarization Index
test. The
groundwall/earth
insulation system
consists of the
wires insulation,
slot liner
insulation,
wedges, varnish
and sometimes
phase paper.
|
|
|
 |
Surge
testing detects
faults in both
inter-turn
windings and
phase-to-phase
insulation
systems. Using
advanced
analog-to-digital
conversion
hardware, the D
series captures
the surge test
waveform,
remembers it,
displays it
indefinitely, and
prints it to a
printer.
|
|
|
 |
The
D series tester
can be used to
test all rotating
fields of a
synchronous motor
by storing the
waveform from a
surge test on one
coil and then
comparing it to
all other
waveforms. It can
also be used on DC
armatures and
fields. The
resulting waveform
can then be
compared to all
other bar-to-bar
or span tests to
detect a winding
fault.
|
|
|
 |
The
D series tester
can be operated on
its own in the
field, and then
data can be
transferred to a
computer running
Baker's Motor Test
Acquisition (MTA)
software for
further analysis.
MTA provides
database
capabilities,
waveform
comparison, report
generation,
printouts, and
other functions
that turns test
data into usable
information. All
options are easily
assessed with
on-screen prompts.
|
|
|
 |
Storage
of test data for
up to 10 motors -
3 surge wave
pattern with
amplitude &
time base, surge
test peak voltage
amplitude, DC
HiPot voltage,
leakage current
and insulation
resistance.
|
|
|
 |
Baker's
QRR reliability
high voltage
design.
|
 |
Zero
start interlock
for tester high
voltage output.
|
 |
Bright,
sharp 5-inch
digital display.
|
 |
HiPot
over-current
safety warning
indicator.
|
 |
Test
leads insulated to
40 kV rating.
|
 |
Dedicated
test leads for
resistance
testing.
|
 |
Test
lead select switch
with all leads
grounded operator
safety position.
|